FailSafe Ultimo wide is available in 100 W/m output as illustrated on the graph to the right. The graph shows the nominal power output at 230V when installed on insulated metal pipes.


FSR Graph

Maximum Continuous Exposure

Temperature (Power ON)

250°C (482°F)

Maximum Permissable Exposure

Temperature (Power OFF)

250°C (482°F)

Minimum Operating Temperature

-40ºC (-40ºF)

Temperature Classification

100FSUw T2 (300°C/572°F)

Power Supply

12 - 277 VAC

Cable Dimensions

FSUw-NF 14.8 x 6.0mm +/- 0.5mm

Minimum Installation Temperature

-40°C (-40°F)

Minimum Bending Radius

FSUw-NF - 35mm

Weight kg/100m

FSUw-NF - 19.5 kg

Maximum Resistance of Protective Braiding

18.2 Ohm/km

Cable Gland Thread Size

FSUw-NF - M25


Maximum Circuit Length (m) for various circuit breaker sizes

Product
Reference

Start-Up
Termperature (°C)

230v

10A

16A

20A

32A

50A

100FSUw


10

18

30

36

58

84

0

18

28

34

56

84

-20

16

24

30

50

76

-40

14

22

28

46

70

For use with Type C circuit breakers to IEC EN60898