FailSafe Ultimo (FSU)
FailSafe Ultimo is an industrial grade self-regulating heating cable that can be used for freeze protection or temperature maintenance of pipework and vessels. It can be cut-to-length on site to match exact piping lengths without any complicated design considerations.
FailSafe Ultimo is approved for use in non-hazardous, and hazardous areas to worldwide standards. Its self-regulating characteristics improve safety and reliability.
FailSafe Ultimo will not overheat or burnout, even when overlapped upon itself. Its power output self-regulates in response to the pipe temperature.
Example of Applications
- Freeze protection of pipework & vessels
- Process temperature maintenance
Benefits
- Can be cut to length
- Output self-regulates in response to pipe temperature
- High outputs to 75W/m at 10ºC
- Inherently Temperature Safe
FailSafe Ultimo is available with a corrosion resistant fluoropolymer outer jacket (FSU-NF).
The installation of FailSafe Ultimo is quick and simple and requires no special skills or tools. Termination, splicing and power connection components are all provided in convenient kits.
-
Product Specification - Maximum Withstand Temperature 250°C (482°F)
FailSafe Ultimo is available in 15, 30, 45, 60, 75 W/m outputs as illustrated on the graph to the right. The graph shows the nominal power output at 230V when installed on insulated metal pipes.
Maximum Continuous Exposure
Temperature (Power ON)
250°C (482°F)
Maximum Permissable Exposure
Temperature (Power OFF)
250°C (482°F)
Minimum Operating Temperature
-40ºC (-40ºF)
Temperature Classification
15FSU - 60FSU T3 (200°C/392°F)
75FSU T2 (300°C/572°F)
Power Supply
12 - 277 VAC
Cable Dimensions
FSU-NF 12.5 x 5.8mm +/- 0.5mm
Minimum Installation Temperature
-40°C (-40°F)
Minimum Bending Radius
FSU- NF - 35mm
Weight kg/100m
FSU-NF - 14.6 kg
Maximum Resistance of Protective Braiding
18.2 Ohm/km
Cable Gland Thread Size
FSU-NF - M20
Maximum Circuit Length (m) for various circuit breaker sizes
Product
ReferenceStart-Up
Termperature (°C)230v
10A
16A
20A
32A
50A
15FSU
10
76
122
154
172
172
0
70
112
140
172
172
-20
62
98
122
172
172
-40
52
82
102
164
172
30FSU10
52
82
102
122
122
0
46
74
92
122
122
-20
40
66
82
122
122
-40
34
54
68
110
122
45FSU10
38
62
76
100
100
0
34
56
70
100
100
-20
30
50
62
98
100
-40
22
34
44
70
100
60FSU10
30
50
62
86
86
0
28
44
56
86
86
-20
20
32
40
62
86
-40
12
18
24
38
60
75FSU
10
22
34
44
70
76
0
16
26
34
54
76
-20
12
18
24
38
60
-40
8
12
14
22
36
For use with Type C circuit breakers to IEC EN60898
-
Approvals & Certifications
FSU
19ATEX3385FSU
CML 19.0128FSU TAE00002KC
FSU
FSU
Chinese