SnoMelt is available in 11 and 17 W/m outputs as illustrated on the graph to the right. The graph shows the nominal power output at 230V when installed on insulated metal pipes.

FSM - nominal power output against pipe temperature

Maximum Surface Temperature

40°C (104°F)

Minimum Installation Temperature

-30°C (-22°F)

Power Supply

1-277 VAC

Cable Dimensions

15.4 x 6.5mm +/- 0.5mm

IP Rating

IP67

Minimum Bending Radius

40mm

Weight kg/100m

15.7 kg

Maximum Resistance of

Protective Braiding

18.2 Ohm/km

Cable Gland Thread Size

M25

Power Factor buried in Sand (wet)

W/m in concrete x 0.9

Power Factor buried in Metal Conduit

W/m in concrete x 0.4

Power Factor buried in Plastic Conduit

W/m in concrete x 0.3

Maximum Circuit Length (m) for various circuit breaker sizes

Product

Reference

Start-Up

Temperature (°C)

230V

6A

10A

16A

20A

SMB

10

14

22

36

44

0

12

18

30

38

For use with Type C circuit breakers to IEC 60898