FailSafe Super is available in 15, 30, 45, 60 and 75 W/m outputs as illustrated on the graph to the right. The graph shows the nominal power output at 230V when installed on insulated metal pipes.


FSR Graph

Maximum Continuous Exposure

Temperature (Power ON)

225°C (437°F)

Maximum Permissable Exposure

Temperature (Power OFF)

225°C (437°F)

Minimum Operating Temperature

-40ºC (-40ºF)

Temperature Classification

15FSS - 60FSS T3 (200°C/392°F)

75FSS T2 (300°C/572°F)

Power Supply

12 - 277 VAC

Cable Dimensions

FSS-CF 11.45 x 5.25mm

+/- 0.5mm

Minimum Installation Temperature

-40°C (-40°F)

Minimum Bending Radius

FSS- CF 35mm

Weight kg/100m

FSS-CF - 13.4 kg

Maximum Resistance of Protective Braiding

18.2 Ohm/km

Cable Gland Thread Size

M20


Maximum Circuit Length (m) for various circuit breaker sizes

Product
Reference

Start-Up
Termperature (°C)

230v

10A

16A

20A

32A

50A


15FSS





10

76

122

154

172

172

0

70

112

140

172

172

-20

62

98

122

172

172

-40

52

82

102

164

172


30FSS

 

10

52

82

102

122

122

0

46

74

92

122

122

-20

40

66

82

122

122

-40

34

54

68

110

122


45FSS

 

10

38

62

76

100

100

0

34

56

70

100

100

-20

30

50

62

98

100

-40

22

34

44

70

100


60FSS

 

10

30

50

62

86

86

0

28

44

56

86

86

-20

20

32

40

62

86

-40

12

18

24

38

60

75FSS

 

10

24

40

50

76

76

0

18

30

38

60

76

-20

14

22

26

42

66

-40

8

12

16

26

40

For use with Type C circuit breakers to IEC 60898