MicroTracer (EMTS) is available in 6.5, 13, 23, 33 and 50 W/m outputs as illustrated on the graph to the right. The graph shows the nominal power output at 230V when installed on insulated metal pipes. |
Maximum Withstand Temperature | 200°C (392°F) |
Maximum Energised Temperature | 190°C (374°F) see workpiece temperature data |
Power Supply | 110-120 VAC, 220-277 VAC |
Cable Dimensions | EMTS-CS 11.4 x 8.2mm +/- 0.5mm EMTS-CF 10.2 x 7.0mm +/- 0.5mm |
Minimum Installation Temperature | -40°C (-40°F) |
Minimum Bending Radius | EMTS-CS - 15mm EMTS-CF - 25mm |
Weight kg/100m | EMTS-CT - 14.3 kg EMTS-CF - 14.3 kg |
Cable Gland Thread Size | M20 |
Product Reference | 115V | 230V |
---|---|---|
6.5 EMTS | 82 | 164 |
13 EMTS | 58 | 116 |
23 EMTS | 44 | 87 |
33 EMTS | 36 | 73 |
50 EMTS | 30 | 59 |
For 10% drop variation |
Heater Nominal Output (W/m) | EMTS-C | EMTS-CS | EMTS-CF |
---|---|---|---|
6.5 EMTS | 190 | 190 | 190 |
13 EMTS | 180 | 185 | 185 |
23 EMTS | 150 | 160 | 160 |
33 EMTS | 110 | 115 | 115 |
50 EMTS | 75 | 80 | 75 |
Surface temperature limits in acordance with EN50014 |