English
Chinese
русский/Russian
Select Language: 


Freezstop Regular (FSR)

Products > Self-Regulating Heaters > Freezstop Regular (FSR)

 

 

Product Features

                                                       ATEX - European Hazardous Area Approval FM - North American Hazardous Area approval CSA - Canadian Hazardous Area Approval
 

Freezstop Regular is an industrial/commercial grade self-regulating heating cable that can be used for freeze protection or temperature maintenance of pipework and vessels in the construction and refrigeration industries.  It can be cut-to-length at site to match exact piping lengths without any complicated design considerations. 

Freezstop Regular is approved for use in non-hazardous, and hazardous areas to world wide standards. Its self-regulating characteristics improve safety and reliability.

Freezstop Regular will not overheat or burnout, even when overlapped upon itself. Its power output self-regulates in response to the pipe temperature.

Freezstop Regular is available with a corrosion resistant thermoplastic outer jacket (FSR-CT). When greater corrosion resistance is required a fluoropolymer outer jacket (FSR-CF) can be supplied.

The installation of Freezstop Regular is quick and simple and requires no special skills or tools. Termination, splicing and power connection components are all provided in convenient kits. See Product, Application and Documentation Links below.

  Click to see larger image
  Thermoplastic Outer Jacket
  Click to see larger image
  Fluoropolymer Outer Jacket
  Click to send us an email Are you interested in Freezstop Regular ?
Click on the Icon to send us an email and someone will contact you.
 
 

Product Specification

Maximum Withstand Temperature 85°C (185°F)

 

Freezstop Regular is available in 10, 17, 25, 31 and 40 W/m outputs as illustrated on the graph to the right.  The graph shows the nominal power output at 230V when installed on insulated metal pipes.  Click on the graph to see a larger version.

  Maximum Continuous Exposure Temperature (Power ON) 85°C (185°F)
  Maximum Permissable Exposure Temperature (Power OFF) 85°C (185°F)
 

Minimum Operating Temperature

-65ºC (-85ºF)

  Temperature Classification Up to 31 W/m T6 (85°C/185°F)
40 W/m or 277V T4 (135°C/275°F)
  Power Supply 12 - 277 VAC
  Cable Dimensions                             FSR-CT 12.95 x 5.95mm +/- 0.5
  Click on the graph to see a larger version.
Nominal power output  against pipe temperature

 

  Minimum Installation Temperature -40°C (-40°F)
  Minimum Bending Radius

 CT            35mm
 CF            35mm

  Weight kg/100m FSR-CT - 12.9 kg
FSR-CF - 14.8 kg
  Maximum Resistance of Protective Braiding       18.2 Ohm/km
  Cable Gland Thread Size M20

 
 
Maximum Circuit Length (m)  for various circuit breaker sizes
 
 
Product
Reference
Start-Up
Termperature (°C)
230v 10A 16A 20A 32A    
 
 
  10FSR 10       136   198   198   198          
    0       122   188  

188

  188          
    -20       108   174   176   176          
    -40       96   154   166   166          
  17FSR 10       92   148   152   152          
    0       84   134   144   144          
    -20       74   118   136   136          
    -40       66   106   128   128          
  25FSR 10       74   118   124   124          
    0       68   108   120   120          
    -20       60   94   112   112          
    -40       52   84   106   106          
  31FSR 10       58   92   112   112          
    0       52   84   104   106          
    -20       46   74   92   100          
    -40       42   66   82   94          
  40FSR 10       46   74   92   98          
    0       42   66   84   94          
    -20       36   58   74   88          
    -40       32   52   66   84          
 
 
For use with Type C circuit breakers to IEC 60898
 

 

Product, Application & Documentation Links

Standard Terminations

DESTU
Terminations
 

 Stripfree Terminations

Associated Products

Associated Applications

Approvals and Certification
FSR
Trace Heating Cable Systems 08ATEX3096X
FSM,FSLe,FSr,FSP,FSS,AHT,MTF,EMTF,HTS1,2 & 3F 3009080
FSM, FSLE, FSR, FSS, FSP, FSPW, FSU, FSUW, DESTU, DESTU-P, DESTU-S, DESTU-E, DESTU-T, DESTU-CT 1547590 Haz Area
FSM, FSLE, FSR, FSS, FSP, FSPW, FSU, FSUw, DESTU, DESTU-P, DESTU-S, DESTU-E, DESTU-T, DESTU-CT, SF-P, SF-T, SF-S and SF–E 1295278 Safe Area
10,17,25 & 31FSR2-CT or CF 17,25,31 & 50FSP2-CF 12,17 & 23FSLe2-CT or CF 114665
FSR SIR 11.0121
EU DoC FSR-C, FSR-CT, FSR-CF
Self Reg Cable TC RU C-GB MЮ62 B 06041
FSR TAE0000272
FSR CNEx19 1555U
Product and Application Datasheets
FSR
Datasheet

Latest News

  • Heat Trace - 'going the distance'      More... | 27 July 2015
  • Heat Trace Ltd November new starters      More... | 21 December 2017
  • National Apprenticeship Awards 2019      More... | 13 December 2019
  • BEWARE - COUNTERFEITERS      More... | 15 June 2010
  • Heat Trace Ltd - July - September new starters      More... | 27 September 2017
  • 2017 New starters      More... | 22 June 2017