Product Features

              ATEX - European Hazardous Area Approval
 
 

PowerHeat (PHT) is a high power, high temperature constant wattage heating cable that can be used for freeze protection and temperature maintainance of pipework and vessels. if has a maximum withstand temperature of 285°C (545°F).

PowerHeat (PHT) can be cut-to-length at site to match exact piping lengths  without any complicated design considerations.  PowerHeat (PHT) can be used to replace MI cables.  Series resistance Mi circuits must be specifically designed for a particular pipe length and cannot be modified to suit site changes.

PowerHeat (PHT) is approved for use in non-hazardous, and hazardous areas to world wide standards.

The installation of PowerHeat (PHT) is quick and simple and requires no special skills or tools. Termination, splicing and power connection components are all provided in convenient kits. See Product, Application and Documentation Links below.

  Click to see larger image
Fluoropolymer Outer Jacket
   
   
   
  Click to send us an email Are you interested in PowerHeat (PHT) ?
Click on the Icon to send us an email and someone will contact you.
 
 
 

Product Specification

Maximum Withstand Temperature 285°C (545°F)

 
 
PowerHeat (PHT) is available in 10, 15, 30, 50 and 70 W/m outputs as illustrated on the graph to the right.  The graph shows the nominal power output at 230V when installed on insulated metal pipes.  Click on the graph to see a larger version.


  Maximum Withstand Temperature 285°C (545°F)
  Maximum Energised Temperature 275°C (527°F)
See Workpiece Temperature table
  Power Supply 12 - 277 VAC
  Cable Dimensions

     PHT..N    10.2 x 7.1 mm
PHT..NF   11.1 x 8.0 mm

  Click on the graph to see a larger version.
Nominal power output  against pipe temperature
  Minimum Installation Temperature -40°C (-40°F)
  Minimum Bending Radius PHT..N     45 mm
PHT..NF   50 mm
  Weight kg/100m

 PHT..N    15 kg
PHT..NF  17 kg

  Cable Gland Thread Size M20

 

 
 
Maximum Circuit Length (m) 
 
Product
Reference
115V 230V
  10PHT 79   152  
  15PHT -   -  
  30PHT 46   88  
  50PHT 35   68  
  70PHT 30   56  
           
           
 
 
For 10% volt drop variation
 
Maximum Workpiece Temperatures (°C)
 
Product
Reference
T6 T5 T4 T3 T2 T1 Safe
 10PHT.NF 39 59 106 186 275 275 275
 15PHT.NF - - - - - - -
 30PHT.NF - - 20 133 243 243 243
 50PHT.NF - - - 64 201 201 201
 70PHT.NF - - - - 147 147 147
               
               
 
 
Surface temperature limits in acordance with EN50014.
 
 NB: Please consult Heat Trace for full
       Technical details.
 
 
 
 

Product, Application & Documentation Links

Standard Terminations

DESTU
Terminations

Associated Products

Associated Applications

Approvals and Certification
PHT 17ATEX3169
Trace Heating Cable Systems 08ATEX3096X
PHT CML 17.0084
EU DoC PHT, PHT-N, PHT-NF
Product and Application Datasheets
PHT
Datasheet
'T' Class Label Instructions

Latest News

  • Heat Trace - 'going the distance'      More... | 27 July 2015
  • Heat Trace Ltd November new starters      More... | 21 December 2017
  • Neil Malone publishes a Heat Tracing Specification + Philosophy      More... | 15 December 2018
  • High Sheriff's awards for Heat Trace 2017/18      More... | 27 March 2018
  • Heat Trace - KORMARINE      More... | 30 November 2017
  • Updated Circuit Length Overview      More... | 09 October 2017