Product Features

               
 
 

MiniTracer (MTF) is a constant wattage cable that can be used for freeze protection and temperature maintainance of pipework and vessels.  It has a maximum temperature of 200°C (392°F).

MiniTracer (MTF) is particularly suited to applications requiring longer circuit lengths than those available for MicroTracer(EMTF).

MiniTracer (MTF) has Factory Mutual (IEEE) approval for use in non-hazardous and hazardous areas.

MiniTracer (MTF) can be cut-to-length at site to match exact piping lengths  without any complicated design considerations.

MiniTracer (MTF) has a fluoropolymer outer jacket (MTF-CF) and so offers excellent corrosion resistant properties.

The installation of MicroTracer (EMTF) is quick and simple and requires no special skills or tools. Termination, splicing and power connection components are all provided in convenient kits. See Product, Application and Documentation Links below.

  Click to see larger image
Fluoropolymer Outer Jacket
(MTF-CF)
   
   
   
  Click to send us an email Are you interested in MiniTracer (MTF) ?
Click on the Icon to send us an email and someone will contact you.
 
 
 

Product Specification

Maximum Withstand Temperature 200°C (392°F)

 
 
MiniTracer (MTF) is available in 6.5, 13, 23, 33 and 50 W/m outputs as illustrated on the graph to the right.  The graph shows the nominal power output at 230V when installed on insulated metal pipes.  Click on the graph to see a larger version.


  Maximum Withstand Temperature 200°C (392°F)
  Maximum Energised Temperature 190°C (374°F)
See Workpiece Temperature table
  Power Supply 208 - 277, 110 - 120 VAC
  Cable Dimensions 10.8 x 6.7 mm
  Click on the graph to see a larger version.
Nominal power output  against pipe temperature
  Minimum Installation Temperature -40°C (-40°F)
  Minimum Bending Radius 35 mm
  Weight kg/100m 15 kg
  Cable Gland Thread Size M20

 

 
 
Maximum Circuit Length (m) 
 
Product
Reference
115V 230V
  6.5MTF 106   212  
  13MTF 75   150  
  23MTF 66   113  
  33MTF 47   94  
  50MTF 38   76  
 
 
For 10% volt drop variation
 
 
 
Maximum Workpiece Temperatures (°C)
 
Product
Reference
T6 T5 T4 T3 T2 T1 Safe
   6.5MTF 50 80 125 190 190 190 190
   13MTF 35 50 100 185 185 185 185
   23MTF - 25 55 160 165 165 165
   33MTF - - 35 115 120 120 120
   50MTF - - - 80 85 85 85
 
 
Surface temperature limits in acordance with EN50014.
 
 
 
 

Product, Application & Documentation Links

Standard Terminations

DESTU
Terminations

Associated Products

Associated Applications

Approvals and Certification
FSM,FSLe,FSr,FSP,FSS,AHT,MTF,EMTF,HTS1,2 & 3F 3009080
EU DoC Minitracer, MTF
Product and Application Datasheets
MTF Datasheet

Latest News

  • Heat Trace - 'going the distance'      More... | 27 July 2015
  • Heat Trace Ltd November new starters      More... | 21 December 2017
  • Neil Malone publishes a Heat Tracing Specification + Philosophy      More... | 15 December 2018
  • High Sheriff's awards for Heat Trace 2017/18      More... | 27 March 2018
  • Heat Trace - KORMARINE      More... | 30 November 2017
  • Updated Circuit Length Overview      More... | 09 October 2017