Freezstop Regular is available in 10, 17, 25, 31 and 40 W/m outputs as illustrated on the graph to the right. The graph shows the nominal power output at 230V when installed on insulated metal pipes.


FSR Graph

Maximum Continuous Exposure

Temperature (Power ON)

85°C (185°F)

Maximum Permissable Exposure

Temperature (Power OFF)

85°C (185°F)

Minimum Operating Temperature

-40ºC (-40ºF)

Temperature Classification

Up to 31 W/m T6 (85°C/185°F)
40 W/m or 277V T4 (135°C/275°F)

Power Supply

12 - 277 VAC

Cable Dimensions FSS-CF

12.95 x 5.95mm +/- 0.5mm

Minimum Installation Temperature

-40°C (-40°F)

Minimum Bending Radius

FSR-CT 35mm
FSR-CF 35mm

Weight kg/100m

FSR-CT - 12.9 kg
FSR-CF - 14.8 kg

Maximum Resistance of Protective Braiding

18.2 Ohm/km

Cable Gland Thread Size

M20


Maximum Circuit Length (m) for various circuit breaker sizes

Product
Reference

Start-Up
Termperature (°C)

230v

10A

16A

20A

32A


10FSR







10


136

198

198

198

0


122

188

188

188

-20


108

174

176

176

-40


96

154

166

166

17FSR







10


92

148

152

152

0


84

134

144

144

-20


74

118

136

136

-40


66

106

128

128

25FSR







10


74

118

124

124

0


68

108

120

120

-20


60

94

112

112

-40


52

84

106

106


31FSR







10


58

92

112

112

0


52

84

104

106

-20


46

74

92

100

-40


42

66

82

94


40FSR










10


46

74

92

98

0


42

66

84

94

-20


36

58

74

88

-40


32

52

66

84

For use with Type C circuit breakers to IEC 60898