Freezstop Low Voltage Wide is available in 12, 17 and 30 W/m outputs as illustrated on the graph to the right.
The graph shows the nominal power output at 12V or 24V when installed on insulated metal pipes.

Maximum Continuous Exposure Temperature (Power ON) | 85°C (185°F) |
Maximum Permissable Exposure Temperature (Power OFF) | 85°C (185°F) |
Minimum Operating Temperature | -40°C (-40°F) |
Power Supply | 1-24 AC or DC |
Cable Dimensions | FLVw-CT 12.95 x 5.95mm +/- 0.5mm FLVw-CF 12.65 x 5.65mm +/- 0.5mm |
IP Rating | IP67 |
Minimum Installation Temperature | -40°C (-40°F) |
Minimum Bending Radius | FLVw-CT - 35mm FLVw-CF - 35mm |
Weight kg/100m | FLVw-CT 11.8 kg FLVw-CF 12.6 kg |
Maximum Resistance of Protective Braiding | 18.2 Ohm/km |
Cable Gland Thread Size | M20 |
Product Reference | Start-Up Temperature (°C) | 24V 6A | 10A | 16A | 20A |
---|---|---|---|---|---|
12FLVw | 5 | 8 | 14 | 18 | |
0 | 8 | 12 | 18 | ||
-20 | 6 | 12 | 16 | ||
-40 | 6 | 10 | 14 | ||
17FLVw | 5 | 6 | 8 | 14 | 16 |
0 | 4 | 8 | 12 | 14 | |
-20 | 4 | 6 | 10 | 14 | |
-40 | 4 | 6 | 10 | 12 | |
30FLVw | 5 | 4 | 6 | 10 | 12 |
0 | 4 | 6 | 8 | 10 | |
-20 | 2 | 4 | 8 | 10 | |
-40 | 2 | 4 | 6 | 8 | |
For use with Type C circuit breakers to IEC 60898-1 |