FSR Graph

FailSafe Ultimo is available in 15, 30, 45, 60, 75 W/m outputs and FailSafe Ultimo Wide is available in 100 W/m output, as illustrated on the graph to the right. The graph shows the nominal power output at 230V when installed on insulated metal pipes.

Maximum Continuous Exposure

Temperature (Power ON)

250°C (482°F)

Maximum Permissable Exposure

Temperature (Power OFF)

250°C (482°F)

Minimum Operating Temperature

-40ºC (-40ºF)

Temperature Classification

15FSU - 60FSU T3 (200°C/392°F)

75FSU T2 (300°C/572°F)

100FSUw T2 (300°C/572°F)

Power Supply

12 - 277 VAC

Cable Dimensions

FSU-NF 12.5 x 5.8mm +/- 0.5mm

FSUw-NF 14.8 x 6.0mm +/- 0.5mm

Minimum Installation Temperature

-40°C (-40°F)

Minimum Bending Radius

FSU- NF - 35mm

FSUw-NF - 35mm

Weight kg/100m

FSU-NF - 14.6 kg

FSUw-NF - 19.5kg

Maximum Resistance of Protective Braiding

18.2 Ohm/km

Cable Gland Thread Size

FSU-NF - M20

FSUw-NF - M25


Maximum Circuit Length (m) for various circuit breaker sizes

Product
Reference

Start-Up
Termperature (°C)

230v

10A

16A

20A

32A

50A

15FSU

10

76

122

154

172

172

0

70

112

140

172

172

-20

62

98

122

172

172

-40

52

82

102

164

172


30FSU


10

52

82

102

122

122

0

46

74

92

122

122

-20

40

66

82

122

122

-40

34

54

68

110

122


45FSU

10

38

62

76

100

100

0

34

56

70

100

100

-20

30

50

62

98

100

-40

22

34

44

70

100


60FSU


10

30

50

62

86

86

0

28

44

56

86

86

-20

20

32

40

62

86

-40

12

18

24

38

60

75FSU

10

22

34

44

70

76

0

16

26

34

54

76

-20

12

18

24

38

60

-40

8

12

14

22

36



100FSUw



10

18

30

36

58

84

0

18

28

34

56

84

-20

16

24

30

50

76

-40

14

22

28

46

76

For use with Type C circuit breakers to IEC EN60898